• Cjx2-D Mechanical Interlocking Reversing Contactor
  • Cjx2-D Mechanical Interlocking Reversing Contactor
  • Cjx2-D Mechanical Interlocking Reversing Contactor
  • Cjx2-D Mechanical Interlocking Reversing Contactor
  • Cjx2-D Mechanical Interlocking Reversing Contactor
  • Cjx2-D Mechanical Interlocking Reversing Contactor

Cjx2-D Mechanical Interlocking Reversing Contactor

Electricity Type: AC
Number of Pole: 3
Phase: 3
Main Circuit Rating Voltage: 380V
Main Circuit Rating Current: 95A
Type: Ac Contactors
Customization:
Gold Member Since 2008

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
LC2-D
Electricity Type.
AC.DC
Transport Package
Standard Export Package
Trademark
KASAN. OEM
Origin
China( Zhejiang)
Production Capacity
3000PCS/Month

Product Description

LC2-D Mechanical Interlocking Contactor

 

 

Application:

 

LC2-D of mechanical chain contacts (hereinafter referred to as mechanical chain contacts)  is in the LC1-D series AC contactor, based on the installation of machinery assembled chain body.  It applies to AC 50 or 60Hz, rated voltage up to 660V and below, rated current up to 95A and the  following circuit, for long-distance direct control of three-phase squirrel-cage motor starting,  stopping and reversing operation. It has a mechanical chain, can ensure the safe operation  of two reverse contacts to prevent short circuit accidents. With JRS1 series thermal relay contacts,  which can be made for motor overload protection.

 

This series of touch products meet IEC60947-4-1, GB14048.4 standards.

 

 

Ambient air temperature of -5 °C ~ 40 °C, and the 24h average does not exceed 35 °C.

Altitude: Altitude less than 2000m.

Atmospheric conditions: 40 °C, relative humidity of the atmosphere does not exceed 50%;  at a lower temperature allows a higher relative humidity, the wettest month of the monthly  minimum temperature level does not exceed 25 °C, the monthly mean maximum relative  humidity of not more than 90%, due to temperature changes in the product of condensation  occurring on the measures must be taken.

 Pollution degree: 3;

 Installation Category: III class;

 Installation conditions: the mounting surface and the vertical gradient is not greater than ± 5 °.

 Impulsive vibration: Product should be installed and used in the absence of a significant  shake and shock, vibrations LC1-D AC Contactor.
Cjx2-D Mechanical Interlocking Reversing Contactor
Cjx2-D Mechanical Interlocking Reversing Contactor
Cjx2-D Mechanical Interlocking Reversing Contactor

Type Rated current
AC-3(A)
Controlled power (KW)
220V 380V 415V 440V 660V
CJX2-09N 9 2.2 4 4 4 5.5
CJX2-12N 12 5.5 5.5 5.5 5.5 7.5
CJX2-18N 18 7.5 7.5 9 9 10
CJX2-25N 25 5.5 11 11 11 15
CJX2-32N 32 7.5 15 15 15 18.5
CJX2-40N 40 18.5 18.5 22 22 30
CJX2-50N 50 15 22 25 30 33
CJX2-65N 63 18.5 30 37 37 37
CJX2-80N 80 22 37 45 45 45
CJX2-95N 95 22 45 45 45 41
CJX2-115N 115 30 55 59 59 80
CJX2-150N 150 40 75 80 80 100
CJX2-170N 170 55 90 100 100 110
CJX2-205N 205 63 110 110 110 129
CJX2-245N 245 75 132 132 132 160
CJX2-300N 300 100 160 200 200 220
CJX2-410N 410 110 220 250 250 280
CJX2-475N 475 147 265 280 280 355
CJX2-620N 620 200 335 400 400 450

 
Type Number of Poles Rated Current
AC-3(A)
Rated Current
In/A
Controlled power(KW)
220V 380V
CJX2-F115N 3P 115 250 200 55
CJX2-F1154N 4P 115 250 200 55
CJX2-F150N 3P 150 355 250 75
CJX2-F1504N 4P 150 355 250 75
CJX2-F185N 3P 185 425 275 90
CJX2-F1854N 4P 185 425 275 90
CJX2-F225N 3P 225 500 315 110
CJX2-F2254N 4P 225 500 315 110
CJX2-F265N 3P 265 630 350 132
CJX2-F2654N 4P 265 630 350 132
CJX2-F330N 3P 330 800 400 160
CJX2-F3304N 4P 330 800 400 160
CJX2-F400N 3P 400 800 500 200
CJX2-F4004N 4P 400 800 500 200
CJX2-F500N 3P 500 1000 700 250
CJX2-F5004N 4P 500 1000 700 250
CJX2-F630N 3P 630 1250 1000 335
CJX2-F6304N 4P 630 1250 1000 335
CJX2-F800N 3P 800 1250 1000 400
 